Please read this installation manual completely before installing the product.Installation work must be performed in accordance with the national wiri
2ENGLISHSAFETY PRECAUTIONS y For electrical work, please have an electrician do the work based on the installation manual and specified circuit diagra
3ENGLISHSAFETY PRECAUTIONS y Do not touch the product with wet hands. - It may cause a fire or electric shock. y Use standard components. - Use of an
4ENGLISHSAFETY PRECAUTIONS CAUTIONInstallation y Securely install the product in an area where the weight of the product can be supported. - The produ
5ENGLISHSAFETY PRECAUTIONS y Transformer selection: - Select an insulating product that complies with IEC61558-2-6 and NEC Class 2. - In addition, con
6ENGLISHSAFETY PRECAUTIONSClass A device NOTESThis equipment has been tested and found to comply with the limits for a Class A digital device, pursuan
7ENGLISHPREPARATIONPREPARATIONThe following provides information on the AC Smart BACnet components, how to install and configure, and other required i
8ENGLISHPREPARATION NOTESThe figures of the components and optionally purchased products shown may differ from the actual components and products.Prod
9ENGLISHPREPARATIONFeatures and FunctionsThe features and functions of AC Smart BACnet are as follows.⑦ ⑧⑪⑩⑨① ③② ⑥④ ⑤<Front><Bottom><Ba
10ENGLISHPREPARATIONInstallation and ConfigurationThis chapter explains how to install and configure AC Smart BACnet.InstallationTo use AC Smart BACne
11ENGLISHPREPARATIONCheck the installation environment and configure the device addressAC Smart BACnet can connect up to 128 devices (including indoor
12ENGLISHPREPARATION...AC Smart BACnetOutdoor UnitsPower Distribution Indicator (PDI)watt-hour meterERVDI/DO, DOKITAWHPAHUIndoor devices 1Configuratio
13ENGLISHPREPARATIONAC Smart BACnet's RS485 connectionAn AC Smart BACnet can have up to 128 indoor units. If there are many outdoor units to be c
14ENGLISHPREPARATIONConnect AC Smart BACnetYou can install AC Smart BACnet and its cables as follows.1. Choose a space for AC Smart BACnet.• Prior t
15ENGLISHPREPARATION4. Connect the RS485 cable,which is located behind the AC Smart BACnet, to the RS485 terminal.ABAHUAB(RS485)ODU CAUTIONThe RS485
16ENGLISHPREPARATION6. Connect the power.• For global models - On the back of AC Smart BACnet, connect the power adapter to the power port.The adapt
17ENGLISHPREPARATION• For US models - At the bottom of AC Smart BACnet, connect the power cord to the power port. NOTESIn some countries, except for
18ENGLISHPREPARATION7. After attaching the hook on the top of the main body to the top of the rear panel installed on the wall, please push the top o
19ENGLISHPREPARATIONConfigure Remote Shutdown FeatureBased on contact closure of Digital Input 1 the AC Smart BACnet can stop all connected devices (i
20ENGLISHPREPARATIONInformation Input MethodTouch the AC Smart BACnet information input box and a touch keyboard at the bottom of the panel will appea
21ENGLISHSTARTINGSTARTINGThis section explains how to connect to the system and register devices to setup the environment (prior to using AC Smart BAC
iEXPLANATORY NOTESENGLISHEXPLANATORY NOTESCopyrightsThe contents of this AC Smart BACnet Installation and User Manual are protected by international c
22ENGLISHSTARTINGRebootingYou can reboot the device as follows.1. Press the power button on the bottom of the unit for 10 or more seconds.• The devi
23ENGLISHLG’S AC Smart BACnet AGREEMENTLG’S AC Smart BACnet AGREEMENTJMT (Joint Matching Test)This is necessary for every independent BMS.The case w
24ENGLISHLG’S AC Smart BACnet AGREEMENT NotesAfter the LG's AC Smart BACnet agreement part, please consult with the experts of BMS.PQNFB17C Hub
25ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet FUNCTIONAL SPECIFICATIONS AC Smart BACnet SummaryThe AC Smart BACnet , in response to the request
26ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Objects - AC Smart BACnet /IPBACnet Point List : Indoor UnitOne indoor unit has a Point List as fo
27ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Point No.Control/monitoringObject Name (XXX : Unit address)Object TypeUnitInactive Active Text- 0
28ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Point No.Control/monitoringObject Name (XXX : Unit address)Object TypeUnitInactive Active Text- 0
29ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Remarks• Point NO. 11. The command executed is transmitted to the A/C regardless of the status of
30ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet BACnet Point List : VentilationOne Ventilation unit has a Point List as follows.Point No.Control/m
31ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Point No.Control/monitoringObject Name (XXX : ventilation address) Object TypeUnitInactive Activ
iiEXPLANATORY NOTESENGLISHProduct FeaturesConvenience• Auto-changeoverAutomatically switches the indoor unit into the correct mode to optimize space
32ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Remarks• Point NO. 11. The command executed is transmitted to the A/C regardless of the status of
33ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet BACnet Point List : AHUOne AHU unit has a Point List as follows.Point No.Control/monitoringObject
34ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Point No.Control/monitoringObject Name (XXX : AHU address)Object TypeUnitInactive Active Text- 0
35ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Point No.Control/monitoringObject Name (XXX : AHU address)Object TypeUnitInactive Active Text- 0
36ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Point No.Control/monitoringObject Name (XXX : AHU address)Object TypeUnitInactive Active Text- 0
37ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Remarks• Point NO. 11. The command executed is transmitted to the A/C regardless of the status of
38ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet BACnet Point List : ODUOne ODU unit has a Point List as follows.AC Smart BACnet ODU Point List ma
39ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet BACnet Point List : AWHPOne AWHP unit has a Point List as follows.Point No.Control/monitoringObjec
40ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Point No.Control/monitoringObject Name (XXX : AWHP address)Object TypeUnitInactive Active Text- 0
41ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet BACnet Point List : GENERALAC Smart BACnet has a GENERAL Point List as follows.Some of GENERAL Po
iiiEXPLANATORY NOTESENGLISHHow to Use This GuidePlease read from beginning to end this User Manual before using AC Smart BACnet. Store this guide so t
42ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Local Definition of Object ID - The instance number is a pair, this consists of the indoor unit No
43ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet AddressObject Type Device No.Product No.Point Instance No. Name33 3 2 1 2 0×02102(8450) ON/OF
44ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet AddressObject Type Device No.Product No.Point Instance No. Name1 3 0 1 2 20102 (131330)ON/OFF
45ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Objects (Modbus-TCP)Supported Function CodeMonitoring and controlling items of air conditioners su
46ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Modbus Point List : Indoor UnitFunction Code : 0x01 and 0x05Register Function NameObject Name (XX
47ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Function Code : 0x03 and 0x06Register Function NameObject Name (XXX : Unit address)Text- 0 Text-1
48ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Remarks• StartStopStatus_XXX1. If there is an operation error, the Present_Value property will be
49ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Modbus Point List : VentilationFunction Code : 0x01 and 0x05Register Function NameObject Name (XX
50ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Function Code : 0x03 and 0x06Register Function NameObject Name (XXX : Ventilation address)Text- 0
51ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Remarks• StartStopStatus_XXX 1. If there is an operation error, the Present_Value property will b
ivENGLISH MEMO
52ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Modbus Point List : AHUFunction Code : 0x01 and 0x05Register Function NameObject Name (XXX : AHU
53ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Function Code : 0x03Register Function NameObject Name (XXX : AHU address)Text- 0 Text-1 Text-2 Te
54ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Function Code : 0x03 / 0x06 Register Function NameObject Name (XXX : AHU address)Text- 0 Text-1 T
55ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Remarks• StartStopStatus_XXX 1. If there is an operation error, the Present_Value property will
56ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Local Definition of Object ID - The instance number is a pair, this consists of the indoor unit No
57ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Case VentFunction Code Device No. Product No. Point Instance No. Name1 0 0 0 0x04000 ON/OFF st
58ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Initialization at the Start UpThe system is designed to automatically recognize the connected air
59ENGLISHFUNCTIONAL SPECIFICATIONS AC Smart BACnet Report FunctionEvent Notification1) Registration of Event Notification DestinationIt is possible
60ENGLISHNOTESNOTESBIBBsAC Smart BACnet Interoperability Building Blocks Supported(BIBBs)Data Sharing BIBBS(□:Notsupported, :Support)BIBB Type Sup
61ENGLISHNOTESBIBB Type Supported AC Smart BACnet Service Initiate ExecuteDS-COV-BData Sharing-COV-B SubscribeCOV ×Confirmed COVNotification×Uncon
vTABLE OF CONTENTSENGLISH1 SAFETY PRECAUTIONS7 PREPARATION7 AC Smart BACnet Overview7 Components8 Product Specifications9 Features and Fu
62ENGLISHNOTESAlarm and Event Management BIBBS(□:Notsupported, :Support)BIBB Type Supported AC Smart BACnet Service Initiate ExecuteAE-N-A Alarm
63ENGLISHNOTESScheduling BIBBS(□:Notsupported, :Support)BIBB Type Supported AC Smart BACnet Service Initiate ExecuteSCHED-AScheduling-A(must supp
64ENGLISHNOTESDevice Management BIBBS(□:Notsupported, :Support)BIBB Type Supported AC Smart BACnet Service Initiate ExecuteDM-DDB-ADevice Managem
65ENGLISHNOTESBIBB Type Supported AC Smart BACnet Service Initiate ExecuteDM-UTC-BDevice Management - UTCTimeSynchronization-B□UTCTime Synchronizat
66ENGLISHNOTESNetwork Management BIBBS(□:Notsupported, :Support)BIBB Type Supported AC Smart BACnet Service Initiate ExecuteNM-CE-ANetwork Manage
67ENGLISHNOTESMulti - state Input Object TypeProperty Identifier Property Datatype AC Smart BACnet Object_Identifier BACnetObjectIdentifier R Obj
68ENGLISHNOTESProperty Identifier Property Datatype AC Smart BACnet Description CharacterString O Devic e_Ty pe CharacterString O Status_Flags
69ENGLISHNOTESAC Smart BACnet Error Response TableError PDUError PDU Error Class Error CodeReading of the object list during the initialization of t
70ENGLISHNOTESAbort PDUReject PDU Reject ReasonUnable to process due to too many requests beyond the capacity.Buffer_Overflow(1)The processing of seg
71ENGLISHTroubleshootTroubleshootControl CodesAC Smart BACnet may display the following control codes during usageControl Code DescriptionS Displayed
viENGLISH MEMO
72ENGLISHTroubleshootError CodeIndoor Device ERV or ERV DX AWHP(Hydro kit) AHU8Hot water thermometer malfunctionOperate smoke control through smoke de
73ENGLISHTroubleshootOutdoor Unit ErrorsError Code Description21 DC peak 22 Max ct (CT 2): Maximum current error23 DC link voltage (low)24 High voltag
74ENGLISHTroubleshootError Code Description55 Communication error (central to main controller)56 Communication error (main to central controller)57 Co
75ENGLISHTroubleshootMultiV 20 Hp, 30 Hp, 40 Hp, errorError CodeDescription100 SLAVE1 static speed compressor 1 discharge temperature surge error101 S
76ENGLISHTroubleshootError CodeDescription133 SLAVE2 outdoor unit sensor (static speed compressor 1 discharge temperature error)134 SLAVE2 outdoor uni
77ENGLISHTroubleshootSuper ErrorsError CodeDescription200 Fan board heat plate temperature sensor error201 Fluid pipe sensor error (fluid pipe sensor
78ENGLISHTroubleshootError CodeDescription233 Fluid pipe sensor error (fluid pipe sensor of HR Unit9 open/short)234 Overcooling inlet sensor error (ov
79ENGLISHTroubleshootPre-Tech Support ChecklistIf the product malfunctions, please check the following before calling the service center.Symptom Check