P/NO : MFL41755815
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
TYPE : CEILING CONCEALED DUCT
MODEL : B62AWYN9L6 / B62AWYU7L6
B70AWYN9L6 / B70AWYU7L6
ENGLISH
Original instruction
www.lg.com
LG Electronics Inc. 2 Wonderland Drive,
Eastern Creek, NSW 2766, Australia
LG Electronics Inc. Changwon 2nd factory
84, Wanam-ro, Seongsan-gu,
Changwon-si, Gyeongsangnam-do, KOREA
Seitenansicht 0
1 2 3 4 5 6 ... 56 57

Inhaltsverzeichnis

Seite 1 - AIR CONDITIONER

P/NO : MFL41755815INSTALLATION MANUALAIR CONDITIONER • Please read this installation manual completely before installing the product.• Installation wo

Seite 2 - TABLE OF CONTENTS

10INSTALLATION PLACEENGLISHSelect space for installing outdoor unit, whichwill meet the following conditions:- No direct thermal radiation from other

Seite 3 - INTRODUCTION

INSTALLATION PLACEENGLISH11Indoor unit installation place- The place shall easily bear a load exceeding four times the indoor unit’s weight.- The plac

Seite 4 - Installation

12INSTALLATION PLACEENGLISHOutdoor unit installation place- If an awning is built over the unit to preventdirect sunlight or rain exposure, make suret

Seite 5 - Operation

INSTALLATION PLACEENGLISH13Obstacle height of discharge side is lower than the unit1. Stand alone installation2. Collective installationHL350 or more1

Seite 6

14INSTALLATION PLACEENGLISHSelecting the location(Outdoor Unit)If the outdoor unit is to be installed close tothe seaside, direct exposure to the sea

Seite 7 - Installation process

PRODUCT INSTALLATIONENGLISH15Case1Position of suspension Bolt- Apply a joint-canvas between the unit andduct to absorb unnecessary vibration.- Apply a

Seite 8 - Features

16PRODUCT INSTALLATIONENGLISH- Insert the set anchor and washer onto thesuspension bolts for locking the suspensionbolts on the ceiling.- Mount the su

Seite 9 - Nomenclature

PRODUCT INSTALLATIONENGLISH17Separating work of the indoorunit (if required)To install the indoor unit, it can be easily sepa-rated into 2 sections by

Seite 10 - INSTALLATION PLACE

18PRODUCT INSTALLATIONENGLISHPlease be sure to secure two section with5 screws. if one of screw is missing, itcould cause unbalance of product or capa

Seite 11

PRODUCT INSTALLATIONENGLISH19Caution for gradient of unit anddrainage pipeLay the drainage pipe hose with a downwardinclination so water will drain ou

Seite 12 - Fence or

2TABLE OF CONTENTSENGLISH3 INTRODUCTION3 Tips for saving energy4 Important safety instructions6 Installation process8 Features9 Environment-friendly a

Seite 13 - 1,500 or

20PRODUCT INSTALLATIONENGLISHLifting method of the outdoor unitCAUTIONBe very careful while carrying the product.• Do not have only one person carry p

Seite 14 - Windbreak

PRODUCT INSTALLATIONENGLISH21The outdoor unit installationThe location of the Anchor bolts- Install at places where it can endure the weight and vibra

Seite 15 - PRODUCT INSTALLATION

22PRODUCT INSTALLATIONENGLISHFoundation for outdoor unit Installation- Fix the unit tightly with bolts as shown below so that unit will not fall down

Seite 16

PIPE CONNECTIONENGLISH23Pipe length and the elevationPIPE CONNECTION• Single OperationIf installed tube is shorter than 15 m, addition-al charging is

Seite 17 - Separating work of the indoor

24PIPE CONNECTIONENGLISHPreparation of PipeMain cause of gas leakage is defect in flaringwork. Carry out correct flaring work in the fol-lowing proced

Seite 18 - Checking the Drainage

PIPE CONNECTIONENGLISH25Preparation Work- Use Knock Outs of Base Pan of the outdoor unit for Left/Right or Bottom pipe drawing outs.Removal Area for L

Seite 19

26PIPE CONNECTIONENGLISHPipe Drawing OutMethod of drawing out pipes on the front side and right side- Proceed with the pipe work as shown in the below

Seite 20 - 40° or less

PIPE CONNECTIONENGLISH27Method of drawing out pipes on the rear side- Proceed with the pipe work as shown in the below figure for rear side pie drawi

Seite 21 - The outdoor unit installation

28PIPE CONNECTIONENGLISH•Do not insulate gas or low pressure pipe and liquid or highpressure pipe together.• Be sure to fully insulate connecting port

Seite 22 - - Remove before Installation

PIPE CONNECTIONENGLISH291m1mABDFGBGDBHIJAEBIABDCInner wall (concealed)Floor (fireproofing) Penetrating portion on fire limit and boundary wallRoof pipe s

Seite 23 - PIPE CONNECTION

INTRODUCTIONENGLISH3• Do not cool excessively indoors. This may be harmful for your health and may consume moreelectricity.• Block sunlight with bli

Seite 24 - Preparation of Pipe

30PIPE CONNECTIONENGLISHForming the pipingForm the piping by wrapping the connecting portion of the indoor unit with insulation materialand secure it

Seite 25 - Preparation Work

LEAKAGE TEST AND EVACUATIONENGLISH31Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.- Pressure in the

Seite 26 - Pipe Drawing Out

32LEAKAGE TEST AND EVACUATIONENGLISHEvacuation- Connect the charge hose end described in thepreceding steps to the vacuum pump to evac-uate the tubing

Seite 27

WIRINGENGLISH33Electrical Wiring- Follow ordinance of your governmentalorganization for technical standard related toelectrical equipment, wiring regu

Seite 28 - Good example

34WIRINGENGLISHIndoor Unit- Open the control box cover and connect the Remote controller cord and Indoor power wires.- Remove the control box cover fo

Seite 29 - Penetrations

WIRINGENGLISH35Connecting the cable to Outdoor UnitRemove the side panel for wiring connection.Use the cord clamp to fix the cord.Earthing work- Case

Seite 30 - Forming the piping

36WIRINGENGLISHCAUTIONIt should be wiring power cables or communication cables to avoid interference with the oil levelsensor. Otherwise, That oil lev

Seite 31 - LEAKAGE TEST AND EVACUATION

WIRINGENGLISH37Communication and Powerwiring cable1) Communication wiring cable- Types : shielding wire- Cross section : 1.0~1.5mm2- Maximum allowable

Seite 32 - Evacuation

38WIRINGENGLISHWiring of main power supplyand equipment capacity 1. Bear in mind ambient conditions (ambienttemperature,direct sunlight, rain water,et

Seite 33 - Power wiring cable

WIRINGENGLISH39Field Wiringu Example Connection of Communication wiring cableIndoor Unit 50Hz, 1Ø, 220-240VOutdoor Unit 50Hz, 3Ø, 380-415V R S T N Swi

Seite 34 - Indoor Unit

4INTRODUCTIONENGLISHImportant safety instructionsREAD ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.Always comply with the following precautions to avoi

Seite 35

40WIRINGENGLISHConnecting the DRED to the outdoor unit- Remove the Front panel and the cover,control by loosingscrew. Tighten a screw at two point as

Seite 36

WIRINGENGLISH41The position of the fixing screwsYellow1 Put the installation paper on the place anddetermine the position and height of thefixing scr

Seite 37 - Communication and Power

42WIRINGENGLISH5feet(1.5meters)Fig.1 Typical locations for remote controller3 Remove the installation paper beforeinstalling the remote controller s

Seite 38

SETTING & TESTENGLISH43How to set Remote Controller's Switch 2NOTE!1. Be sure to set the value refering table 1. Unexpected set value will ca

Seite 39 - Field Wiring

44SETTING & TESTENGLISH1 Press button to appear button onthe screen. mode.2 Press the button for 3secs.3 Press the button.4 Set the volume of

Seite 40 - (PQDSBCDVM0)

SETTING & TESTENGLISH45If entering into ESP setup mode by using button, it indicates as the picture below.2Select ESP fan step by pressi

Seite 41 - Main frame

46SETTING & TESTENGLISH① For test run, carry out the cooling oper-ation firstly even during heating sea-son. If heating operation is carried outfi

Seite 42 - (1.5meters)

SETTING & TESTENGLISH478) Never fail to equip a leakage breakerwhere it is wet or moist.9) The following troubles would be causedby voltage drop-d

Seite 43 - SETTING & TEST

48SETTING & TESTENGLISHError Indicator• This function indicates types of failure in self-diagnosis and occurrence of failure for air condi-tion.•

Seite 44 - 3 Press the button

SETTING & TESTENGLISH49Error Indicator (Outdoor)Outdoor ErrorEx) Error 21 (DC Peack)1 Time 1 Time 12 Times2 Times2 Times1 Sec.2 Sec. 2 Sec.1 Sec.

Seite 45 - ESP step

INTRODUCTIONENGLISH5• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compressair or Oxygen and do not use Flam

Seite 46

50SETTING & TESTENGLISHFunction Description Setting Off Setting On DefaultSW1 CommunicationCommunication BetweenIndoor & OutdoorCommunicationN

Seite 47 - HAND OVER

SETTING & TESTENGLISH51Outdoor UnitIf you set the Dip Switch when power is on, the change in setting is notapplicable. The changing setting is ena

Seite 48 - Indoor Unit Error

52SETTING & TESTENGLISHDry Contact(Only AC 24V)- Fix dry contact on the indoor control boxcover.- Connect dry contact(CN-CC) to IndoorPCB(CN-CC) w

Seite 49 - Error Indicator (Outdoor)

ACCESSORY GUIDEENGLISH53WLAN module installation (PWFMDD101)1. Connect USB wire harness to USB connector. Beside the control box of the product.2. Con

Seite 50 - Dip switch setting

54ACCESSORY GUIDEENGLISHDamper Controller(PBZC80)- Open the cover of indoor unit control box and damper controller(Figure 1)- Assemble the damper cont

Seite 51 - Outdoor Unit

ACCESSORY GUIDEENGLISH55NOTE!PDRCUDC0 is a remote controller connected to 8 damper controller.Remote Temperature Sensor(PQRSTA0)- After deciding where

Seite 52 - ACCESSORY GUIDE (PQDSB1)

56ACCESSORY GUIDEENGLISHTwo wired remote controller- All wired remote controllers are displayed on identical information.- Last used wired romote con

Seite 54 - Damper Controller(PBZC80)

6INTRODUCTIONENGLISHCAUTIONInstallation• Always check for gas (refrigerant) leakage after installation or repair of product. Low refrigerant lev-els m

Seite 55

INTRODUCTIONENGLISH7The foundation must be level evenOutdoor unit foundation workAvoid short circuits and ensure sufficient space is allowed for servic

Seite 56 - Two wired remote controller

8INTRODUCTIONENGLISHAir outlet ventsAir intakeventsAir outlet ventsAir intake ventsRemote controller(Accessory)Features

Seite 57

INTRODUCTIONENGLISH9- The refrigerant R-410A has the property ofhigher operating pressure in comparison withR22. Therefore, all materials have the ch