INSTALLATION MANUAL
AIR
CONDITIONER
www.lg.com
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.
[
Representative
]
LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[
Manufacturer
]
LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si,
Gyeongsangnam-do, KOREA
For more information, Refer to the CD or LG Web site (www.lg.com).
WALL MOUNTED
Original instruction
ENGLISH
ITALIANO ESPAÑOL
FRANÇAIS DEUTSCH
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
Seitenansicht 0
1 2 3 4 5 6 ... 26 27

Inhaltsverzeichnis

Seite 1 - CONDITIONER

P/NO : MFL69485402INSTALLATION MANUALAIRCONDITIONERwww.lg.comPlease read this installation manual completely before installing the product.Installatio

Seite 2 - TIPS FOR SAVING ENERGY

10INSTALLATIONENGLISHFixing Installation Plate (SV)The wall you select should be strong and solidenough to prevent vibration.1 Mount the installation

Seite 3 - IMPORTANT SAFETY INSTRUCTIONS

INSTALLATION11ENGLISHOutside diameterABurrs removal1. Completely remove all burrs from the cutcross section of pipe/tube.2. While removing burrs put t

Seite 4

12INSTALLATIONENGLISH3 Pull back the tubing holder.4 Remove pipe port cover and positioningthe tubing* The feature can be changed according totype of

Seite 5

INSTALLATION13ENGLISHCAUTIONInstallation Information. For right piping.Follow the instruction above.!Bad case- Following bending case from right to le

Seite 6 - TABLE OF CONTENTS

14INSTALLATIONENGLISH<Right side piping>2 Secure the cable onto the control boardwith the cable retainer.3 Tape the tubing pipe, drain hose and

Seite 7 - INSTALLATION PARTS

INSTALLATION15ENGLISHWrap the insulation materialaround the connecting portion.1 Overlap the connection pipe insulation ma-terial and the indoor unit

Seite 8 - INSTALLATION MAP

16INSTALLATIONENGLISHChecking the DrainageTo check the drainage.1 Pour a glass of water on the evaporator.2 Ensure the water flows through the drainho

Seite 9

INSTALLATION17ENGLISHInstallation of filters1 Pull out the [Allergy free filter + Triple Filter] from the separately packed plastic bag.2 Detach the tw

Seite 10 - Flaring Work

18INSTALLATIONENGLISHCAUTIONThe Power cord connected to the unit should be selected according to the following specifica-tions. !CAUTIONAfter the conf

Seite 11 - Connecting the Piping

INSTALLATION19ENGLISHDIP Switch SettingIndoor UnitOutdoor UnitIn case that the products meet specific conditions, “Auto addressing” function can start

Seite 12 - Connecting the Piping (SV)

2TIPS FOR SAVING ENERGYENGLISH• Do not cool excessively indoors. This may be harmful for your health and may consume moreelectricity.• Block sunligh

Seite 13 - Installation of Indoor Unit

20ENGLISHINSTALLATIONGroup Control SettingGroup Control 1n Wired remote controller 1 + Standard Indoor UnitsSome products have no DIP switch on PCB. I

Seite 14 - Adhesive

21ENGLISHINSTALLATIONGNDSignal12 VSlaveSlaveMasterorDonʼt connect serial 12V lineLGAP Network SystemMasterSlaveMasterDisplay Error MessageGroup Contro

Seite 15 - Type 'C' screw

22ENGLISHINSTALLATIONGNDSignal12 VLGAP Network SystemFAUMasterFAUorSlaveMasterSlaveMasterMasterDisplay Error MessageDisplay Error MessageNMGroup Contr

Seite 16 - Checking the Drainage

23ENGLISHINSTALLATION2 Remote Controln Wired remote controller 2 + Indoor unit 1LGAP Network SystemMasterMasterSlaveGNDSignal12 VSlaveSlaveSlaveorDisp

Seite 17 - Wiring Connection

24ENGLISHINSTALLATIONAccessories for group control settingIt is possible to set group control by using below accessories.Indoor unit 2 EA +Wired remot

Seite 18

25ENGLISHINSTALLATIONThe A-weighted sound pressure emitted by this product is below 70 dB.** The noise level can vary depending on the site.The figure

Seite 19 - DIP Switch Setting

26INSTALLATIONENGLISH

Seite 21 - Group Control 2

IMPORTANT SAFETY INSTRUCTIONS3ENGLISHIMPORTANT SAFETY INSTRUCTIONSREAD ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.Always comply with the following pr

Seite 22 - Group Control 3

4IMPORTANT SAFETY INSTRUCTIONSENGLISH• Always ground the product.- There is risk of fire or electric shock.• Install the panel and the cover of contro

Seite 23 - 2 Remote Control

IMPORTANT SAFETY INSTRUCTIONS5ENGLISH• Use a vacuum pump or Inert (nitrogen) gas when doing leak-age test or air purge. Do not compress air or Oxygen

Seite 24

6TABLE OF CONTENTSENGLISH2 TIPS FOR SAVINGENERGY3 IMPORTANT SAFETYINSTRUCTIONS7 INSTALLATION PARTS7 INSTALLATION TOOLS8 INSTALLATION MAP9 INSTALLATION

Seite 25 - Model Designation

INSTALLATION PARTS7ENGLISHINSTALLATION TOOLSChassisNameShapeInstallation plateDrain hoseType "A" screwType "C" screw -The feature

Seite 26 - INSTALLATION

8INSTALLATION MAPENGLISHINSTALLATION MAPVinyl tape (Wide)• Apply after carrying out a drainage test.• To carry out the drainage test, remove the

Seite 27

INSTALLATION9ENGLISHSelect the best Location - There should not be any heat or steam nearthe unit.- Select a place where there are no obstaclesaround