www.lg.comINSTALLATION MANUALAIR CONDITIONER • Please read this installation manual completely before installing the product.• Installation work must
10Connecting Pipes • Align the center of the piping and sufficientlytighten the flare nut by hand.• Finally, tighten the flare nut with torque wrenc
Installation Manual 11ENGLISHConnecting Pipes Forming the pipingForm the piping by wrapping theconnecting portion of the indoorunit with insulation
12Leakage test and Evacuation Leakage test and EvacuationAir and moisture remaining in the refrigerant system have undesirable effects as indicated
Installation Manual 13ENGLISHLeakage test and Evacuation1. Connect the charge hose end described in thepreceding steps to the vacuum pump to evacuate
14Precautions when laying power wiringUse round pressure terminals for connections to the power terminal block.When none are available, follow the ins
Installation Manual 15ENGLISHTest running Test running1. PRECAUTIONS IN TEST RUNNING• The initial power supply must provide at least 90% of the rat
Outdoor Unit ErrorEx) Error 21 (DC Peak)1 Time 1 Time 1 Time2 Times2 Times2 Times1 Sec.2 Sec. 2 Sec.1 Sec. 1 Sec. LED01G(RED) LED02G(GREEN)Self-diagno
Installation Manual 17Installation Guide at the SeasideENGLISHInstallation Guide at the Seaside1. Air conditioners should not be installed in areas w
18Installation Guide at the SeasideThe A-weighted sound pressure emitted by this product is below 70 dB.** The noise level can vary depending on the s
[Representative] LG Electronics Inc. EU Representative Krijgsman 1, 1186 DM Amstelveen, The Netherlands[Manufacturer] LG Electronics Inc. Changwon 2nd
2Single A Air Conditioner Installation ManualCONTENTSSafety Precautions ...
Safety PrecautionsInstallation Manual 3ENGLISHTo prevent the injury of the user or other people and property damage, the following instructionsmust b
4Safety PrecautionsDo not install the product at a place that thereis concern of falling down.• Otherwise, it may result in personal injury.Use cautio
Installation Manual 5Safety Precautions ENGLISHn InstallationInstall the drain hose to ensure that draincan be securely done.• Otherwise, it may ca
If installed tube is shorter than 10 m, additional charging is not necessary. *Additional Refrigerant = ((A) -10) x Additional refrigerant (g) 6Outdoo
Installation Manual 7The outdoor unit installationThe outdoor unit installation* Make sure the rubber bushes are Properly used in knock-out holes aft
8Piping length and the elevation• The installation piping is connectable in 3directions.(refer to figure 1)Preventing foreign objects from entering(re
Installation Manual 9ENGLISHMain cause of gas leakage is defect in flaringwork. Carry out correct flaring work in thefollowing procedure.Cut the pipe